Date | Hour | ID | Note |
---|---|---|---|
Wed 01/Mar/06 | 11:00 | GG | After a long RECOVERING, Locked loops 1, 3-8. Pressure in these loops ~ 0.39 b. Weight 23.6 kg. |
^ | 11:37 | IAC | RUN. Standard procedure. |
^ | 12:45 | SC | Recovery |
^ | 17:00 | GG | Dummy staves switched OFF. Heaters damaged . System in STOP. No damages to the cooling lines. |
^ | 17:30 | GG | OFF loops 1, 3-8. System in RECOVERING. |
Thu 02/Mar/06 | 9:30 | GG | Weight 23.54. LOCKED loops 1, 2-10 @ ~0.39 b. |
^ | 10:28 | GG | RUN. |
^ | 10:36 | GG | Sector 0 ON , 12/12 HS |
^ | 10:40 | GG | Weight 18.25 kg, stable. |
^ | 11:15 | GG | Heater checked. All the 11 resistance still in specification (~5 Ohm, see paper logbook for details). Serious deformation of the carbon fibre support. |
^ | 16:16 | GG | Weight 18.15. Pressure in loop 1 0.74 b. Other still ~0.39 b. |
^ | 19:23 | SC | Recovery |
Fri 03/Mar/06 | 09:45 | GG | Weight 23.36 kg. Pressure in loop 1 0.66 b. Leak in a valve? Other still ~0.39 b. |
^ | 09:58 | GG | Temperature tube loop 10: injection and vapours 21°C (measured with quickTEMP, infrared thermometer). Loop 2 locked and 10 open. RUN |
^ | 10:12 | GG | Weight 18.2kg. |
^ | 10:30 | GG | Weight 17.4kg. linear decreasing. Temperature not changed. |
^ | 10:36 | GG | Weight 17.3kg. Temperature vapours 20°C. |
^ | 12:19 | GG | Weight 15.3kg. Temperature vapours 20°C. In ALARM for low volume in the condenser. RECOVERING |
Tue 07/Mar/06 | 08:00 | GG | General power cut. |
Thu 09/Mar/06 | 18:16 | GG | Starting up the system after the power cut. Chiller restarted, PVSS rebooted, System reset. Loop 4 ON. RECOVERING. |
Fri 10/Mar/06 | 15:00 | GG | LEAK TEST. |
Mon 13/Mar/06 | 09:52 | GG | Leak rates all high. Opened all the loops and RECOVERING. Weight 22.9 kg. |
Tue 14/Mar/06 | 16:54 | GG | LEAK TEST. |
^ | 17:12 | GG | The loops are NOT locked during the test, but closed. SW bug? |
^ | 17:26 | GG | Leak rates of ~ 1.8 mb/min. Weight 21.9 kg. Loops locked. STAND-BY. Pressure in the loops ~0.37 b |
Wed 15/Mar/06 | 15:08 | GG | System in RUN during the morning, up to now. |
^ | 15:09 | GGRT | Loop 2 closed, loop 10 open. RUN. Screwed the pressure sensor and the vacuum valves of pump 8a. |
^ | 15:50 | GGRT | Loop 2 open. RECOVERING. |
^ | 17:00 | GGRT | Refilling started during the recovering. Cylinder put at the top of a footboard. |
^ | 17:54 | GGRT | STOP. Refilling in progress. Acceleration of the refilling rate. |
^ | 19:00 | GGRT | Refilling completed at 32.6 kg. |
Fri 24/Mar/06 | 11:53 | GG | System in ALARM for a general power cut. Restored the compressor driver. Weight 32.5kg. Closed all loops. System in STOP. |
Wed 29/Mar/06 | 12:00 | GG | System found OFF for a local power cut. Restored. Weight 32.5 kg. Locked all loops. System in RECOVERING. |
^ | 15:19 | SC | System put in Run mode and after open loop2 |
^ | 15:39 | SC | System put in RECOVERING |
^ | 16:06 | SC | System put in Run Mode |
^ | 18:59 | SC | System put in RECOVERING |
Thu 30/Mar/06 | 09:31 | GG | Weight 30.3 kg. ~ 0.5 b in the closed loops. All loops open. |
^ | 14:54 | SC | Close all loops, put the system in run mode, then open the loop2 |
^ | 15:40 | SC | System in Recovering |
^ | 19:11 | SC | Allarm: "Tank Leak", aknoledge the allarm. Then system in Recovering |
Fri 31/Mar/06 | 10:20 | SC | System put in Run Mode and then open loop2 |
^ | 11:49 | SC | System put in Recovering |
ID | Name |
---|---|
GG | Gianluca Guaglio |
IAC | Ivan Amos Cali |
SC | Simone Ceresa |
RT | Rosario Turrisi |